Used in underfloor heating/cooling systems and designed to provide thermal insulation between the installation and the rest of the building structure, as well as support for laying pipes in a single/double serpentine or spiral pattern.
Reference standard: SR EN 13163:2012
Designation according to EN 13163 – EPS-EN 13163-T2-L3-W3-S5-P10-DS(N)5- DLT(1)5-BS250-CS(10)150
Material: expanded polystyrene (EPS).
Laminated film.
Color: white EPS polyethylene. Black laminated film.
Pipe laying size: 16–18 [mm]
Panel area: 0.5 [m²]
Actual panel size: 1030 x 530 [mm x mm]
Usable panel size: 1000 x 500 [mm x mm]
Total height: 39 [mm].
Stud height: 24 [mm]
Installation pitch: 50 [mm].
Thermal conductivity: 0.035 [W/mK]
Thermal resistance: 0.43 [m²K/W]
Maximum load: 75 kPa [7500 kg/m²]
Fire reaction Euroclass according to EN 13501-1: E
Fire reaction Euroclass according to DIN 4102: B2